RO Water Softening Desalination Treatment Plant for Boiler Feed Water Supply
Description of RO Water Treatment Plant
The reverse osmosis device is a technique to purify the saline water with the action of pressure difference between two sides of semi-permeable membrane. It is called reverse osmosis, as it is counter to natural penetration direction. Difference material have different osmotic pressures.
The reverse osmosis can remove more than 97% of the soluble salt and above 99% of the colloid, microorganism, particles and organic materials, becoming the best choice in the engineering of modern purified water.
The most highlighted features includes low energy consumption, no pollution, simple technique, high-quality water, convenient operation and maintenance.
Technical Data of RO Drinking Water Purifier
No. |
Item |
Reverse Osmosis Filtration System |
1 |
HS code |
8421219990 |
2 |
Salt rejection rate |
98.5% |
3 |
Working pressure |
0.8-1.6Mpa |
4 |
Voltage |
200v/50Hz,380V/50Hz,etc. Customized as requested. |
5 |
Material |
SS Skid frame, CPVC pipes, FRP tanks, PVC pipes, etc. |
6
|
Raw water |
TDS |
TDS<5000 ppm |
Temperature |
2-40 |
Recovery rate |
50-75% |
9 |
Water-out conductivity
(us/cm)
|
<200 us/cm for 1st pass RO system;
<10 us/cm for 2nd pass RO system.
|
10 |
Product Keywords |
RO reverse osmosis plant |
11 |
Reverse osmosis (RO) membrane |
Dow Filmtech or Toray |
12 |
High pressure pump |
Groundfoss or CNP pump |
13 |
Inlet water SDI |
<5 |
14 |
Inlet water PH |
3--10 |
Features of Reverse Osmosis Water Filtration
(1) High salt rejection rate: 99%, and high recovery rate up to 75%.
(2) CIP cleaning system, automatic flushing when systems stops, thus prolong the membrane’s service life.
(3) High and low voltage protection for lack water warning, full water stop. Emergency online monitor security of equipment operation.
(4) PLC control of water level, pumps, valves, conductivity, PH, flow meter, working pressure on control panel.
(5) Various combination of technical purify process. RO, Double passes of RO, RO+EDI, UF+RO+EDI, etc. The technical design would be confirmed according to water quality you need.
(6) Core components imported from world famous brand, Dow Filmtec, Hydranautics, Toray or other equivalent brand.
Consumable Replacement of Reverse Osmosis Filter
It depends on practical feed water quality and the filters you choose. When product water outputs decreases 15%, the TDS of product water increases 15% or transmembrane pressure increases 15%, then you need to replace the consumables of RO unit to guarantee good shape performance and prolonging service time.
No. |
Consumables |
Performance life span |
1 |
Quartz sand |
3 years |
2 |
Activated carbon |
3 years |
3 |
Water softening resin |
1 years |
4 |
Pp filter |
6 months |
5 |
Ro membrane |
24-36 months, according to feed water quality
|
6 |
UV lamp |
1 year |